If a home was built or had circuits added between the mid-1960s and the mid-1970s, some of its outlets, switches and lights may be wired with solid aluminum instead of copper. Aluminum wiring is not by itself a reason to walk away from a house, but its connections need attention. The U.S. Consumer Product Safety Commission (CPSC) treats older aluminum branch wiring as a real fire risk and has published clear guidance on how to repair it.
This guide explains what aluminum branch wiring is, why its connections can overheat, the warning signs to watch for, what the finding means in an inspection report, and which repairs are considered permanent.
What aluminum branch wiring is
A copper shortage in the mid-1960s led builders to use more aluminum wire. According to the CPSC, homes built before 1965 are unlikely to have aluminum branch circuit wiring, but cables installed between 1965 and the mid-1970s, in new homes, in additions and in rewired or new circuits, may contain it. Plenty of homes in Fargo, Moorhead and West Fargo were built or remodeled during those years, so it is worth knowing what to look for.
“Branch wiring” means the smaller circuits that feed outlets, switches and light fixtures. That is different from the larger aluminum conductors still used today for service entrance cables, electric ranges and clothes dryers. The CPSC’s repair recommendations apply to the small branch circuits, not to those larger wires.
You can often identify aluminum branch wiring by:
- Markings on the cable jacket. Look for “AL” or “ALUMINUM” printed on the outer sheathing, which is sometimes visible in an unfinished basement or at the electrical panel.
- The color of the wire. Where the bare conductor is visible, aluminum looks dull silver or gray rather than copper-colored.
Cable marked “CU-clad” or “copper-clad” is a different product, and the CPSC notes that its repair recommendations do not cover it.
Why aluminum wiring connections overheat
The trouble with aluminum wiring is almost always at the connections, not in the wire running through the walls. Aluminum expands and contracts more than copper as it heats and cools, and it forms an oxide layer on its surface. Over years of use, connections at outlets, switches, light fixtures and splices can loosen and overheat.
The numbers behind the concern come from research done for the CPSC. The Franklin Research Institute found that homes built before 1972 and wired with aluminum were 55 times more likely to have one or more outlet connections reach “fire hazard conditions” than homes wired with copper.
Just as important, the CPSC notes that these failures seldom give easy-to-spot warning signs and can happen without any earlier symptoms. That is why aluminum wiring calls for a professional evaluation even when everything seems to work.
Warning signs of aluminum wiring problems
The CPSC lists these signs of possible overheating:
- Cover plates on outlets or switches that feel warm or hot to the touch
- Flickering lights
- Circuits that stop working
- The smell of burning plastic at outlets or switches
If you notice any of these, the CPSC’s advice is clear: have a qualified electrician find the cause, and do not try to fix it yourself.
What this finding means in an inspection report
During a home inspection, we look at the wiring visible inside the electrical panel and at other accessible locations. When we see solid-conductor aluminum branch wiring, we note it and recommend an evaluation of the electrical system by a licensed electrician familiar with aluminum wiring repairs.
A visual inspection cannot check every connection hidden inside walls and electrical boxes. The electrician can open devices, look at the condition of the connections and recommend a repair plan. A thermal imaging scan can sometimes show a connection that is running hot, but it cannot rule out problems at connections that are not under load at the time.
Aluminum wiring often shows up in homes with other older electrical equipment, so it is worth reading about Federal Pacific electrical panels and Pushmatic electrical panels if your home has one of those as well.
Repairs the CPSC considers permanent
The CPSC has evaluated the common repair methods. Here is how they compare:
| Repair method | What it involves | CPSC view |
|---|---|---|
| Rewire with copper | Replacing the aluminum branch circuits with new copper wiring | “The best method available,” but the most disruptive |
| COPALUM crimp connectors | A short copper wire (pigtail) joined to each aluminum wire with a crimped sleeve, installed with a special tool by electricians trained by the manufacturer | Recommended permanent alternative to rewiring |
| AlumiConn connectors | A setscrew connector that joins the aluminum wire to a copper pigtail | Next best alternative when COPALUM is not available; shorter track record |
| Twist-on connector pigtails | Ordinary twist-on wire connectors used to join copper pigtails | Not an acceptable permanent repair |
| CO/ALR outlets and switches | Devices rated for use with aluminum wire | Better than standard devices, but “at best, an incomplete repair” |
The CPSC considers twist-on pigtails and CO/ALR devices emergency, temporary repairs only, to be followed by a complete permanent repair as soon as possible. It also highly recommends hiring a qualified electrician for the work.
How to stay safe with aluminum wiring
- Get a full evaluation. Ask a licensed electrician to look at the whole system, and ask how every aluminum connection will be addressed, including outlets, switches, light fixtures and splices.
- Don’t swap outlets or switches yourself. Standard devices are not made for aluminum wire, and a do-it-yourself repair can create the very connection problem you are trying to avoid.
- Watch for warning signs. Warm cover plates, flickering lights, dead circuits or a burning smell are reasons to call an electrician right away.
- Keep your smoke alarms working. Test them regularly, as you should in any home.
- Keep the paperwork. Save the electrician’s invoice showing what was repaired. Future buyers and insurers often ask.
If you are shopping for an older home, our article on what to expect when buying a home built before 1970 covers other features that are common in homes from that era.
Aluminum wiring: common questions
Is aluminum wiring safe?
Aluminum branch wiring can work for years, but its connections are more likely to overheat than copper connections. The CPSC treats it as a fire risk and recommends permanent repairs by a qualified electrician.
How do I know if my house has aluminum wiring?
Look for “AL” or “ALUMINUM” printed on the cable jacket, or silver-colored wire at the electrical panel. Homes built or rewired between about 1965 and the mid-1970s are the most likely to have it. An electrician or home inspector can confirm it.
Can I just replace outlets with CO/ALR devices?
The CPSC calls CO/ALR devices “at best, an incomplete repair.” They are better than standard devices, but they don’t fix splices or every type of connection in the system, and the CPSC considers them a temporary measure.
Should I buy a house with aluminum wiring?
Many people do. Before closing, have a licensed electrician evaluate the wiring and explain the recommended repair, so you know what you are taking on.
Does aluminum wiring have to be completely replaced?
Not always. The CPSC considers rewiring with copper the best option, but properly installed COPALUM or AlumiConn pigtail connections are also accepted as permanent repairs.
Have questions about the electrical system in a home you are buying? Learn more about our home buyer’s inspection, or schedule a homeowner inspection for the home you already own.