GFCI and AFCI Protection: Where You Need It and How to Test It

GFCI and AFCI protection are two of the most important electrical safety upgrades in a home, and missing GFCI protection is one of the most common electrical findings in our inspections. A GFCI (ground-fault circuit interrupter) shuts off power in a fraction of a second to protect people from electric shock. An AFCI (arc-fault circuit interrupter) shuts off a circuit when it senses dangerous arcing that can start a fire. The short answer: have GFCI protection at every outlet near water, in the garage, outside and in unfinished basements, test GFCIs and AFCIs once a month, and have a licensed electrician add or replace them.

This guide explains GFCI vs AFCI, where GFCI outlets are required today, how to test them, and what it means when an inspection report notes missing or faulty GFCI protection.

GFCI vs AFCI: what’s the difference?

Electrical Safety Foundation International (ESFI) puts it simply: GFCIs protect people from electric shock, and AFCIs protect against electrical fires caused by arcing faults.

GFCI. A GFCI watches the current going out on a circuit and coming back. The U.S. Consumer Product Safety Commission (CPSC) explains that if the two differ by as little as 0.006 amps, the GFCI cuts the power “faster than a blink of an eye.” That difference usually means current is leaking somewhere it shouldn’t, possibly through a person. The CPSC credits GFCIs with a key role in reducing electrocutions. A GFCI can be built into an outlet (receptacle), a circuit breaker or a portable cord.

AFCI. An arc is a spark that jumps across a loose connection, a damaged cord or a nail through a wire. An AFCI breaker or outlet senses the pattern of a dangerous arc and shuts off the circuit before it can start a fire. ESFI notes that the CPSC estimates AFCIs could prevent more than 50 percent of electrical fires each year. Electrical failures and malfunctions were involved in an estimated 45,210 U.S. home structure fires a year from 2010 to 2014, according to NFPA figures cited by the Minnesota Department of Labor and Industry.

The two devices do different jobs, and current code calls for both. Some devices, called dual-function AFCI/GFCI, combine them.

Where are GFCI outlets required?

GFCI requirements have grown with each edition of the National Electrical Code (NEC). The CPSC lists when the main locations were added: outdoors (1973), bathrooms (1975), garages (1978), kitchens (1987), crawl spaces and unfinished basements (1990), and laundry and utility sinks (2005).

Under the 2023 NEC, as summarized by Electrical Construction & Maintenance (EC&M), dwelling GFCI protection covers 125- to 250-volt receptacles in:

  • Bathrooms
  • Garages and accessory buildings
  • Outdoors
  • Crawl spaces at or below grade
  • Basements
  • Kitchens, and other areas used for food or beverage preparation or cooking
  • Within 6 feet of the top inside edge of any sink
  • Within 6 feet of a bathtub or shower stall
  • Laundry areas
  • Boathouses
  • Indoor damp and wet locations

Older homes were built to the code of their day, and the NEC generally applies to new work. North Dakota and Minnesota each adopt the NEC on their own schedule, so your city’s electrical inspector or a licensed electrician can tell you what applies to a specific project.

Where AFCI protection is required

EC&M’s summary of the 2023 NEC lists AFCI protection for 120-volt, 15- and 20-amp circuits feeding kitchens, family rooms, dining rooms, living rooms, bedrooms, closets, hallways, laundry areas and similar rooms. AFCI protection is not required in bathrooms, garages or outdoors. When existing wiring in those rooms is modified, replaced or extended, the code generally calls for adding AFCI protection to that circuit. That is why an electrician may add AFCI breakers during a remodel.

GFCI protection missing: what it means in an inspection report

When we find outlets without GFCI protection in a kitchen, bathroom, garage, exterior, unfinished basement or laundry area, we note it in the inspection report and recommend upgrading for safety. It’s most common in older homes built before those locations required it. We test outlets with a plug-in tester, and we check whether an outlet is protected by a GFCI outlet upstream or a GFCI breaker in the panel. A standard-looking outlet can still be protected if it’s downstream of a GFCI, so look for a “GFCI Protected” sticker.

GFCI receptacle tested faulty

The GFCI didn’t trip when tested, or didn’t reset. The CPSC says a GFCI that doesn’t pass its test is not working or wasn’t installed correctly, and should be replaced.

Ungrounded GFCI outlet not labeled

A GFCI can safely replace an old two-prong outlet on a circuit with no ground wire, and it still protects against shock. But it doesn’t provide a ground for surge protectors or electronics, so the CPSC says it must carry the supplied label “No Equipment Ground, GFCI Protected.”

How to test a GFCI outlet

The CPSC recommends testing every GFCI after installation, at least once a month, after a power outage and according to the manufacturer’s instructions. Blackouts and other power disturbances can sometimes damage a GFCI.

  1. Plug a lamp into the outlet and turn it on.
  2. Press the TEST button. The lamp should go off.
  3. Press RESET. The lamp should come back on.
  4. If the lamp doesn’t go off when you press TEST, or doesn’t come back on after RESET, the GFCI isn’t working. Replace it.

ESFI recommends testing AFCIs the same way, monthly with the TEST button on the breaker or outlet, and replacing any AFCI that doesn’t trip. If an AFCI or GFCI keeps tripping on its own, it may be doing its job. Have an electrician find the cause rather than replacing the device with a standard one.

How to fix missing GFCI or AFCI protection

  1. List the outlets that need protection. Start with the kitchen counters, bathrooms, garage, exterior, unfinished basement, laundry and any sink.
  2. Call a licensed electrician. The CPSC says GFCI breakers should be installed by a qualified electrician and outlets only by people with the right knowledge and skills; ESFI says AFCIs should only be installed by a licensed electrician.
  3. Pick the right device. One GFCI outlet at the start of a circuit can protect the outlets downstream. A GFCI or AFCI breaker in the panel protects the whole circuit. A dual-function breaker does both.
  4. Label it. Downstream outlets get “GFCI Protected” stickers, and ungrounded GFCIs get “No Equipment Ground.”
  5. Test monthly. Put it on the same calendar reminder as your smoke alarm test.

Outdoor outlets also need a proper weatherproof cover. Our post on exterior outlet covers explains which one you need.

GFCI and AFCI: common questions

Do I have to upgrade an older house to GFCI and AFCI?

Generally not, unless you’re doing electrical work that triggers it. The NEC typically applies to new construction and major renovations. But adding GFCI protection near water is an inexpensive safety upgrade we recommend in every home.

What does “GFCI protection missing” mean?

It means outlets in a location where GFCI protection is now standard, such as a kitchen, bathroom, garage or exterior, weren’t protected when tested. It’s a safety upgrade for a licensed electrician.

Can I put a GFCI on a two-prong outlet?

Yes. The CPSC notes that a GFCI works on ungrounded two-slot outlets and can replace them, as long as it’s labeled “No Equipment Ground.” An ungrounded GFCI outlet that isn’t labeled should get the label. It protects people from shock but doesn’t ground your electronics.

Why does my GFCI keep tripping?

A GFCI trips when it senses current leaking, often from moisture in an outdoor outlet, a worn appliance cord or a damaged tool. Unplug everything on the circuit, reset it, and plug items back in one at a time. If it still trips, call an electrician.

Watch it happen: a failing sump pump tripping the GFCI outlet it was plugged into, from one of our inspections, on our Facebook page.

Is a GFCI breaker better than a GFCI outlet?

Both give the same shock protection. A breaker protects the whole circuit from the panel; an outlet is easier to reach for testing and resetting.

What if a GFCI receptacle tests faulty?

Replace it. There’s no set lifespan for a GFCI, which is why the monthly test matters: a GFCI that doesn’t trip and reset isn’t protecting anyone.

Buying an older home? Our posts on aluminum wiring, knob and tube wiring and what to expect in a home built before 1970 cover other electrical findings, and our guide to smoke and carbon monoxide alarms covers the rest of home fire safety. To have your outlets checked, schedule a homeowner inspection or learn about our home buyer’s inspection.